Stress Control Tube Problems: Why 10-35 kV Terminations Fail

Most 10-35 kV termination faults do not start inside the cable. They start at the stress-control tube, at the point where the insulation shield is cut back. This page walks through the failures we see in returned terminations and the field data that tells you what actually went wrong.

1. What the Stress Control Tube Actually Does

A medium-voltage termination ends the insulation shield at a sharp cut. At that edge, the electric field concentrates many times above the average stress. If nothing redistributes it, corona starts at the cut and erodes the insulation until breakdown. The heat-shrink stress control tube is a field-grading layer with a controlled dielectric constant (typically εr 12-30 for resistive grading, or 6-8 for capacitive grading) that spreads the stress over a longer distance along the insulation surface.

Two things must both be right for it to work: the tube must sit exactly over the shield cut-back, and there must be no air at the interface. Almost every field failure we analyse fails one of these two.

2. Symptom → Root Cause → Fix

Symptom on siteMost likely root causeField fix
Tube slid off the cut, bare insulation visibleSupplied ID too large; tube recovered but did not bite the semiconRe-size on prepared cable OD; tube must recover onto semicon edge with 10-15 mm overlap
Tube too short, gap at the topLongitudinal shrink cut the piece shortAdd 10-15% to cut length; verify recovered length on a sample
Rough, pitted surface under the tube after removalAir void ionised under PD over monthsSmooth semicon edge, clean surface, heat centre-out to expel air
Discharge tracking along the tube surfaceContamination or moisture on the insulation surfaceWipe with approved solvent, control humidity, avoid touching the surface after cleaning
Corona at the cut edge despite correct positionSemicon cut not clean; loose strands leftCut shield with a sharp blade, remove every loose strand, sand any burr

These are the patterns, but the numbers matter. A 26/35 kV termination that runs clean at 30 kV with a good stress-control interface will begin to discharge as soon as even a 0.5 mm air pocket sits at the cut — the stress magnification is that sharp.

3. Positioning Is a Measurement Job, Not a Visual Job

The most common error is placing the tube "by eye" over where the installer thinks the shield ends. Do this instead:

On critical feeders, photograph the marked position before and after recovery so the QA record shows the cut-back line matched the tube edge.

4. Air Voids, Semicon Edges and Surface Cleanliness

An air gap between the semicon, the tube and the insulation is a miniature capacitor with a very low breakdown voltage. Under normal service voltage the gap ionises, and the local discharge erodes the insulation polymer. The erosion is slow — months, not minutes — which is why the fault appears long after commissioning and gets blamed on the cable.

Three habits remove the risk:

5. Which Test Catches It

An AC or DC withstand test will often pass even when a stress-control interface is marginal, because a short test does not sustain the PD long enough to fail. The test that separates good from bad is a partial-discharge measurement at power-frequency voltage. It detects the pico-coulomb-level discharges at the cut that precede breakdown. For critical 26/35 kV switchgear feeders, specify a PD test at 1.5 U0 and log the pC reading.

Related: Heat Shrinkable Stress Control Tube · MV Termination Partial Discharge Prevention · MV Accessories by Voltage

Frequently asked questions

Why does my stress control tube keep sliding off the shield cut-back?

Either the supplied inner diameter was sized too large, or the cut-back mark was placed past the tube's designed recovery point. Re-size on prepared cable OD and confirm recovery with 15 mm overlap each side.

How much does longitudinal shrink matter for a stress control tube?

Polyolefin field-grading tubes shorten 5-15% during recovery. Cut to the bare minimum and the tube pulls back off the cut, leaving a bare gap where corona starts. Add 10-15% to the cut length.

Can an air void under the stress control tube cause partial discharge?

Yes. An air pocket at the semicon/tube/insulation interface concentrates stress and ionises, producing PD that erodes the insulation. Smooth the semicon, clean the surface, heat centre-out.

What test catches a mispositioned stress control tube?

A partial-discharge test at power-frequency voltage, with the cut-back marker verified, reveals discharge at the interface. A DC or AC withstand test alone may pass while PD is already present.

Specifying a stress control tube for a 10-35 kV termination?

Send the cable OD, insulation diameter, shield construction and voltage class. We return a sized recommendation with the correct cut length.

Request a Quote

Related: Browse materials · Browse applications · All guides