Busbar Insulation Retrofitting: Switchgear

Insulating busbar in a cabinet that is already built is a different job from insulating it on the panel builder's bench. If you are specifying a heavy-duty busbar insulation sleeve for switchgear rather than assembling at the bench, these are the three routes that work and the inputs that decide between them.

Copper busbars covered in heat-shrink casing, showing insulated bends and joints

The problem this page solves

A retrofit starts from a cabinet that already exists. The bars are bent and bolted, the phase spacing is fixed by the enclosure, and the outage window is measured in hours rather than shifts. Insulation has to go on without stripping the bus, or the project has to be built around a shutdown.

Three failures drive the work: phase-to-phase short circuit where bars pass close together, pollution flashover tracking along an exposed bar surface, and accidental contact where a panel door opens onto live copper. Animal ingress into a cabinet adds a fourth: a small carcass bridging two phases is a common cause of an unplanned trip.

Tape wraps are cheap and creep under heat cycling. Moulded shrouds fit one geometry. Heat-shrink casing conforms to the bar, holds a continuous wall and covers the bend. Size it from the system voltage and the bar dimensions, not from a catalogue range alone.

Technical specification and cross-identification

Every figure below is the published value on the Wellele product page for that item. Cross-identification lists the nearest catalogue family from other suppliers, for identification only.

Wellele Series-TypeFormVoltage classSize basisReference standardsCross-identification
WLL-BBN-10Heat-shrink casing, medium-thick wall8.7/15 kVRecovered ID Φ20–180 mmASTM D2671, -55 to +125 °CRaychem/TE BMM · 3M BBI-A · DSG-Canusa Deray-HB
WLL-BBN-24Heat-shrink casing (catalogued at RFQ)15–24 kVQuoted on bar drawingQuoted on bar drawingRaychem/TE BBIT · 3M BBI-6A · Deray-HBM
WLL-BBN-35Heat-shrink casing, thick wall26/35 kVRecovered ID Φ30–200 mmASTM D2671, -55 to +125 °CRaychem/TE BBIT (35 kV class) · 3M BBI-10A · Deray-HBT
WLL-BBN-SNAPSplit silicone wall, clip-on, no heat10 kV / 35 kVBar width and thicknessConfirmed at quotationNo published cross-reference
WLL-BBN-BOXMoulded flame-retardant box and coverAmbient ≤50 °CT / X / I / S / L layoutGB/T 13539.1No published cross-reference

Cross-identification is a starting point for a like-for-like enquiry, not a statement of equivalence. Competitor designations are trademarks of their respective owners. WLL-BBN-24 has no page of its own and is quoted by code.

Selected products for this application

8.7/15KV Busbar Heat Shrink Casing MPG10

Cross-linked PE · 8.7/15 kV · ID Φ20–180 mm · ASTM D2671

26/35KV Busbar Heat Shrink Casing MPG35

Cross-linked PE · 26/35 kV · ID Φ30–200 mm · thick wall

10kV/35KV Snap-On Insulating Tube

Silicone · split wall · clips onto an installed bar, no heat

What to send for a sized recommendation

System voltage

Highest system voltage and the equipment's rated voltage class, not the nominal figure alone.

Bar dimensions

Width, thickness, corner radius, and whether the bar is flat, channel or tubular.

Run and access

Straight length and bends, plus whether the bar can be removed from the cabinet.

Phase spacing

Centre-to-centre distance and the clearance you have to achieve.

Environment

Indoor, outdoor or polluted-substation air, and the pollution level your design assumes.

Outage window

How long the cabinet can be down and whether a heat source is permitted on site.

Engineering questions we are asked

Can I insulate busbars that are already installed in a live cabinet?

Two routes. The snap-on split tube clips over an installed bar without heat and without disassembly, which suits switchgear that cannot be stripped down. Heat-shrink casing needs the bar accessible and a heat source, so it is normally fitted during a planned outage or at the panel builder's bench. If neither fits your outage window, send the bar drawing and we will say which route is realistic instead of bidding both.

Which voltage class do I order for an 11 kV or a 33 kV system?

Order on the system's highest voltage, not the nominal figure: an 11 kV system maps to the 8.7/15 kV casing and a 33 kV system to the 26/35 kV casing. Voltage is only half the decision, because the bar dimensions and the phase spacing in the cabinet set the wall and the profile as well.

How do I size casing for a rectangular copper bar?

Work from bar width and thickness against the recovered ID, not from the bar's diagonal. The 8.7/15 kV range covers recovered ID 20 to 180 mm and the 26/35 kV range covers 30 to 200 mm. Send width, thickness, corner radius and the run length and we return the casing size with cut lengths.

Does the insulation stop flashover in polluted or coastal air?

It lengthens the surface creepage path, which is what pollution flashover depends on, but the anti-tracking duty is set by the compound grade and the profile rather than by the fact that the bar is covered. Tell us indoor, outdoor or polluted-substation air and the pollution level you design to, and we confirm whether the standard casing grade is enough or a different construction is needed.

Can casing be used to reduce phase-to-phase clearance?

Yes, that is one of its main jobs. Covering the bar raises the withstand between adjacent phases, so a cabinet can be built tighter or an existing one brought back into clearance. The clearance figure itself has to be recalculated by your engineer, because the casing changes both the surface path and the air gap. We supply the component data for that calculation, not a system clearance claim.

Send the bar dimensions and the outage window

Voltage class, bar width and thickness, phase spacing, indoor or outdoor air, and how long the cabinet can be down. We return a sized recommendation with cut lengths, lead time and a sample.